Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
183
View - Auto Detect
Detects the address and baud rate of the local RTU. Auto Detect will first try to communicate with the local
RTU at the baud rate configured in Configuration, PC Setup.
Baud rate of Toolbox does not match the local RTU.
Select Yes to check other baud rates.
Address and baud rate of the local RTU has been detected.
Select Yes to update Toolbox.
Baud rate of Toolbox matches local RTU.
Auto Detect returns address of the local RTU.
Toolbox could not detect the local RTU at any baud rate. Reasons:
Incorrect COM port or IP Address (if using Ethernet)
configured in Configuration, PC Setup
The PC cable is not connected or is faulty.
The PC cable is not connected to an RTU serial (or Ethernet)
port.
The RTU port has been incorrectly configured. The RTU
configuration and ladder logic can be cleared by removing the
battery link on the back of the CPU module and waiting for
about 2 minutes. Note: the battery link for an LP-1/2/3 is inside
the case.