Kingfisher PLUS+ Installation Manual 2.6
www.cse-semaphore.com/mykingfisher
8.13 IO-4 Wiring Diagram
There are three separate isolated groups, one for the analog input, one for the digital input and one for
the digital output. Each group may be powered from a separate source. Analog input channel 1 can be
factory modified to support a strain gauge input.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
INTERNAL
CIRCUITRY
7 A
DI Common
DO CH 2
DI CH 7
DI CH 8
DO CH 1
LINK *
0 V
+E (optional)
+S (optional)
-E (optional)
AI CH 1 or -S
Wiring Examples
AI CH 2
DI CH 1
+24 V Ou tput
DI CH 2
DO Common
DI CH 3
DI CH 6
DI CH 4
DI CH 5
+E (5 V)
+S
-E (0 V)
-S
Strain gauge input
(special order only)
0-50 mV
AI CH x
+24 V
Output
2-wire transmitter
(powered by module)
0 V
AI CH x
+24 V
Output
3-wire transmitter
(powered by module)
-
+
Analog
Input
+
-
Analog
Input
4-wire transmitter
(powered by module)
0 V
AI CH x
+24 V
Output
PWR
+
-
Analog
Input
External Power
Supply. Note: polarity
can be reversed.
DI CH x
DI
Common
External power
supply. Note: polarity
can be reversed.
+
DO CH x
LOAD
DO
Common
+
FIELD CONTACT
DI CH x
+24 V
Output
Powered by module
FIELD CONTACT
DI Com.
0 V
Link
POWER
SUPPLY
POWER
SUPPLY
DC pow ered inputs
and low voltage AC
inputs can both be
used on the one
module.
* Optional link for DC SUPPLY
ONLY. Enables fuse fail LED
‘FU’ on module. CAUTION!
When link is installed, a
maximum voltage of 30 V AC or
DC can be used to power the
common.
4-wire transmitter
(powered externally)
+
-
AI CH x
0 V
Analog
Input
PWR
POWER
SUPPLY
+
-
3-wire transmitter
(powered externally)
+
-
AI CH x
0 V
Analog
Input
PWR
POWER
SUPPLY
+
-
AI CH x
2-wire transmitter
(powered externally)
0 V
+
-
Analog
Input
POWER
SUPPLY
+
-