4. Backplane Setup
If a single backplane is being used then the switches on the backplane do not need to be changed.
When linking two backplanes, please set the backplane switches as shown below (for backplane
revisions 2.1, 2.2 and 3.2). A data cable is required to link the backplanes. If a backplane does not
have its own power supply, a power cable will also be required to connect it to a powered backplane.
The examples below show linking for BA-xx PLUS (revision 3.2) backplanes. When linking BA-xx
PLUS backplanes (green Phoenix data connectors) with the older BA-xx backplanes (black Harwin
data connectors), BAC-INT-0x data cables are used. These cables have a Phoenix connector on one
end and a Harwin connector on the other. All data cables are straight through and do not contain
crossovers. To link two older BA-xx backplanes, a BAC-0x data cable is used.
Note: different rack numbers are required to
avoid clashing of the slot addresses.
Both backplanes are
powered from the
PC-1 in slot 13.
The PC-1 is
powered by a
PSU-3 connected to
the BA-4
Note:same rack numbers can be used since each backplane
has different slot addresses (1 to 6 and 13 to 16).
Both backplanes
are powered
using a PS-11 in
any slot
(typically slot 1)
Same settings apply for BA-12
Note: different rack numbers are required to avoid
clashing of the slot addresses.
Each backplane requires its own PS-11/21 power
supply module (typically installed in the left slot).
Note: a single supply can be used to power both
backplanes using a BPC-0x power cable if the total
current load of the supply is not exceeded.
Same settings apply for BA-12